YJV32 7 Core 0.6/1 kV Steel Wire Armoured XLPE Power Cable for Buried and Trench Routes
YJV32 steel wire armoured power cable
,7 core 0.6/1 kV XLPE cable
,buried trench route power cable
YJV32 7 Core 0.6/1 kV Steel Wire Armoured XLPE Power Cable for Buried and Trench Routes
Seven copper cores, XLPE insulated, wrapped in a full concentric layer of galvanised fine steel wires and finished with a black PVC sheath. Built for routes where the cable is pulled through a duct or dropped down a shaft, then buried under fill that carries traffic.
- 0.6/1 kV (Um 1.2 kV)
- 7 x 35 mm2
- 7/2.52 mm copper
- XLPE 0.9 mm
- 90 C continuous
- approx. 38 mm OD
01 / Specifications
Key specifications
Values follow GB/T 12706.1-2020 and GB/T 3956. Current ratings are three core baseline figures at 25 C; overall diameter and weight are calculated from the layer build-up.
Section and rating table
Conductor structure per GB/T 3956 class 2; ratings at 25 C, single circuit, three core baseline.
Ambient correction for 90 C conductor: 30 C x 0.96, 35 C x 0.92, 40 C x 0.88, 45 C x 0.83. Grouping: two circuits x 0.85, three x 0.75, four x 0.68 when spacing is under 2 x diameter.
02 / Construction
Six layers, from core to surface
Each layer is there for a reason that shows up on site, not on a data sheet.
- 1. Copper conductor, class 2 stranded 7/2.52Stranded rather than solid so the seven cores can still pass a duct bend, while holding the 0.524 ohm/km limit at 20 C.
- 2. XLPE insulation, 0.9 mmA thermoset: it does not soften and retreat at 90 C, so insulation thickness and withstand level survive the bending of lay-up, armouring and sheathing.
- 3. Fillers and binder tapeThe seven core bundle has a lumpy outline; fillers make it round and the tape holds it, so the steel wires lay evenly instead of riding up on a high core.
- 4. Extruded bedding layerGives the wires a flat seat, so no wire presses directly on an insulated core, and cushions the insulation against wire movement in bending.
- 5. Galvanised fine steel wire armourTakes tensile load (long duct pulls, hanging vertical drops) and point load (stones, backfill, tools) away from the cores. YJV22 steel tape covers only the radial crush.
- 6. Black PVC outer sheath, approx. 2.2 mmSeals the wires from soil and moisture and takes the abrasion of pulling; the black compound carries the weathering duty in outdoor runs.
03 / Where it goes
Installation conditions this construction is specified for
Duct crossings under roads and rail
The cable is drawn whole into embedded concrete or PVC ducts, pull tension lands on the wire layer, and both ends are sealed after the pull. Duct bore is checked at min. 1.5 x cable diameter.
Cable trenches and buried feeders in plant yards
Laid on a sand bed with a warning tile above, along a route crossed by forklifts and trucks, in backfill that carries rubble. The 145 A / 155 A baseline is corrected for ground temperature and grouping.
Vertical drops in pump wells and shafts
Self weight hangs on the armour; the cable is cleated to the wall at intervals down the shaft and at the head, with bends kept above 12 x diameter.
Outdoor direct burial between substation and boards
Route passes backfilled ground, construction debris layers and unpaved surface, with bends and joint bays in between; buried sections are rated from the 155 A figure.
04 / Standards and tests
What each standard actually checks
No certification claim is made beyond the reports listed in the quotation.
Routine test reports (conductor resistance, voltage test, insulation resistance) are issued against the drum number. Type test reports travel with the drum when the order scope includes them.
05 / Selection
Decide in six questions
06 / Buyer questions
FAQ
Can I bury YJV32 directly in the ground without a duct?
Yes, direct burial is one of its normal uses, provided the trench has a sand bedding layer and the backfill is cleared of sharp rubble. If the soil is rocky or the route carries vehicle load, keep the sand layer and put a warning tile above the cable. Burial depth and bedding thickness come from the local installation code, not from the cable standard.