YJV32 3 Core 0.6/1 kV Steel Wire Armoured Power Cable for Three Phase Feeder Runs
YJV32 3 core armoured power cable
,0.6/1 kV steel wire armoured cable
,three phase feeder power cable
| YJV32 / 3 core / 0.6/1 kV / 3 x 35 mm2 | GB/T 12706.1-2020 | 90 C | R 12 x D |
|
THREE PHASE FEEDER CABLE YJV32 3 Core 0.6/1 kV Steel Wire Armoured Power Cable for Three Phase Feeder RunsThree copper cores, XLPE insulation, a full layer of galvanised steel wires and a black PVC oversheath. 34.8 mm diameter, 1670 kg/km, 145 A in air and 155 A buried - figures that apply to this construction as it stands, with no multi-core derating on top. 0.6/1 kV 3 x 35 mm2 Cu 7/2.52 XLPE 0.9 mm 34.8 mm OD |
3 core YJV32 cut at both ends: XLPE insulated copper cores, bedding, galvanised steel wire armour, PVC oversheath. |
Drummed supply, illustrative image. Standard drum 500 m, cut to order. |
Sand bedding and warning tile in a trench, illustrative image of the direct burial condition. |
01 / SPECIFICATIONS
3 x 35 mm2, 0.6/1 kV
Structure and temperature values per GB/T 12706.1-2020 and GB/T 3956. Diameter, weight and current rating are maker reference values for 3 x 35 mm2 at 25 C, single circuit, three core laying.
| Model | YJV32 - copper conductor, XLPE insulated, fine galvanised steel wire armoured, PVC sheathed |
| Rated voltage | 0.6/1 kV (Um = 1.2 kV) |
| Cores x cross section | 3 x 35 mm2 - series also covers 3 x 25, 50, 70 and 95 mm2 |
| Conductor | Bare copper, class 2 stranded 7/2.52 mm; DC resistance max. 0.524 ohm/km at 20 C |
| Insulation | XLPE, nominal thickness 0.9 mm |
| Screen | No metallic screen. Galvanised fine steel wire armour provides the mechanical protection layer |
| Sheath | PVC, black, nominal thickness approx. 2.0 mm (standard dimension class) |
| Standard | GB/T 12706.1-2020; conductor to GB/T 3956 |
| Operating temperature | 90 C continuous; 250 C short circuit for 5 s max.; ambient at laying min. 0 C |
| Minimum bending radius | 12 x overall diameter - about 418 mm at 34.8 mm |
| Reference current rating | 145 A in air / 155 A direct buried at 25 C, single circuit, three core laying. Applies to this construction directly |
| Overall diameter | 34.8 mm |
| Weight | 1670 kg/km |
| Drum length | 500 m standard, cut to order |
Three core series
| Section mm2 | Conductor | Insulation mm | R20 max. ohm/km | In air A | Buried A |
| 25 | 7/2.14 | 0.9 | 0.727 | 118 | 127 |
| 35 | 7/2.52 | 0.9 | 0.524 | 145 | 155 |
| 50 | 19/1.78 | 1.0 | 0.387 | 177 | 187 |
| 70 | 19/2.14 | 1.1 | 0.268 | 224 | 234 |
| 95 | 19/2.53 | 1.1 | 0.193 | 273 | 283 |
Corrections before sizing: ambient 40 C x 0.88, 45 C x 0.83; grouping 2 circuits x 0.85, 3 x 0.75, 4 x 0.68 where spacing is under 2 x diameter.
02 / CUTAWAY
What is under the black sheath
Six layers, stripped back from left to right.
| 1 Copper 7/2.52, class 2 Seven wires rather than a solid rod, so the three cores survive being bent into a duct while the 20 C resistance stays under 0.524 ohm/km. |
2 XLPE insulation 0.9 mm Chosen over PVC because three cores packed in one sheath run hot; 90 C conductor rating buys 20 C more headroom at the same section. |
| 3 Fillers and binder tape Three round cores leave triangular voids; filled and taped to a circle so the steel wires do not sink into the valleys and thin the sheath. |
4 Extruded bedding Wires ride on the bedding, not on insulation, so bending and long term vibration wear the bedding instead of the core surface. |
| 5 Galvanised steel wire armour Takes pull in duct runs and self weight in risers, plus point load from backfill. The zinc coat is the part that corrodes first in wet soil. |
6 PVC oversheath approx. 2.0 mm Moisture and abrasion barrier, taken from the standard dimension class for a 34.8 mm cable; final thickness is stated on the works order. |
03 / WHERE IT GOES
Circuits this cable fits
Three loaded cores, no neutral - every case below is a balanced three phase run.
|
Package substation to distribution panelOut of the transformer box on tray, down into a duct, then into the panel. Two 90 degree bends set the 418 mm bending radius limit.
|
Pump and fan feedersBalanced motor load, no neutral. Laid in trench then buried, with a waterproof joint and a low level of continuous vibration on the tray run.
|
|
Ducts under a yard slabPrecast PVC ducts, bore checked at min. 1.5 x diameter (52 mm and up); pulling tension goes into the wire layer, not the cores.
|
Risers between floorsSelf weight hangs on the armour, cleated at each floor, routed away from the fire main that shares the shaft.
|
04 / STANDARDS AND TESTS
What is actually tested
| GB/T 12706.1-2020 | Structure and dimensions, insulation and sheath thickness, armour and oversheath requirements, electrical performance, core identification. |
| GB/T 3956 | Conductor class 2 strand construction and the 20 C DC resistance limit - 0.524 ohm/km at 35 mm2. |
| GB/T 2951.11 / 2951.12 | Tensile strength, elongation at break and air oven ageing retention of insulation and sheath compounds. |
| GB/T 3048.4 | DC resistance of the finished conductor. |
| GB/T 3048.5 | Insulation resistance. |
| GB/T 3048.8 | AC power frequency voltage test on the completed cable. |
| GB/T 18380.12 | Vertical flame spread on a single cable; run on the flame retardant ZR- variant, not required for the plain type. |
| GB/T 17650.1 / 17651.2 | Halogen acid gas and smoke density; only the low smoke zero halogen WDZ-YJY32 variant is assessed to these. |
Routine test report (conductor resistance, voltage test, insulation resistance) is issued per drum number. Type test reports are supplied when the order scope includes them.
05 / SELECTION
Three cores, or four?
The one decision that changes the product more than section size does.
| Construction | Conductors | Use when |
| 3 core YJV32 | 3 equal phases | Balanced three phase load only, no single phase branch on the circuit |
| 3+1 YJV32 | 3 phases + smaller neutral | Small single phase share; saves copper against a full size neutral |
| 4 core YJV32 | 4 equal conductors | Substantial single phase load, or neutral sized to match the phase |
| 7 core (custom) | Multi circuit / mixed | Several small three phase groups in one sheath; runs hotter at the same section |
| Buried under traffic or rubble? | YJV32 wire armour. Steel tape (YJV22) covers radial crush only. |
| Vertical, self supporting? | YJV32. Tape armour is not specified to hang weight in a riser. |
| Single phase load on the circuit? | Then not 3 core - move to 3+1 or 4 core. |
| Ambient above 40 C or grouped? | Apply 0.88 and 0.85 before fixing the section; do not read the table value straight. |
| Wet, saline or termite ground? | YJV33 with PE oversheath, or an anti-termite sheath construction. |
| Tunnel or escape route? | WDZ-YJY32 low smoke zero halogen, not this PVC sheath. |
06 / BUYER QUESTIONS
FAQ
Do I need a neutral conductor for this cable?
No, YJV32 3 core carries three phases only. If the circuit feeds single phase loads, a neutral is required and the correct product is 4 core or 3+1. A 3 core leaves that load without a return path.
Can a 3 core cable carry unbalanced load?
It tolerates a small unbalance, but the design assumption is a balanced three phase load. Sustained unbalance pushes one or two cores above the rating and changes the thermal profile of the bundle; if the single phase share is significant, specify 3+1 instead.
What is the difference between 3 core, 3+1 and 4 core?
3 core has three equal phase conductors and no neutral. 3+1 adds a reduced neutral for a limited single phase share. 4 core uses four equal conductors where the single phase load is substantial or the neutral must match the phase section.
How many amps will 3 x 35 mm2 carry?
145 A in air and 155 A direct buried at 25 C, single circuit. Correct for ambient temperature (x 0.88 at 40 C) and grouping (x 0.85 for two circuits, 0.75 for three) before the section is fixed. No multi-core derating applies here, because the figures are already quoted for a three core construction.
Does the steel wire armour reduce the current rating?
Not in a three core cable. Eddy losses from steel armour matter in single core AC circuits, where the armour sits in the field of one conductor. In a three core cable the phase currents sum close to zero, so the table figures stand.
What drum length and bending radius should we plan for?
500 m is the standard drum, shorter lengths cut to order. Minimum bending radius is 12 x overall diameter, about 418 mm at 34.8 mm, applying both during the pull and after the cable is cleated.
Note. Structure and temperature values follow GB/T 12706.1-2020 and GB/T 3956. Diameter 34.8 mm, weight 1670 kg/km and the 145 A / 155 A ratings are reference values for 3 x 35 mm2 at 25 C; sheath thickness is taken from the standard dimension class. Final values are stated on the works order. Two photographs are illustrations, not project records.
YJV32 3 core 0.6/1 kV steel wire armoured power cable, 3 x 35 mm2.