YJV32 4 Core 0.6/1 kV Armoured Cable with Neutral for Risers and Sub Mains
YJV32 4 core armoured cable
,0.6/1 kV power cable
,armoured cable for risers
YJV32 4 Core 0.6/1 kV Armoured Cable with Neutral for Risers and Sub Mains
Four cores: three phases and a full size neutral, XLPE insulated, armoured with a layer of galvanised steel wires, black PVC oversheath, rated 0.6/1 kV.
It suits the run that carries both three phase power and a single phase branch: a riser serving several floors, a sub main to a floor board, a panel link where lighting and socket circuits share one cable. The fourth core is a neutral, not a spare phase, so its section is checked against the actual neutral current instead of being assumed.

Section through the cable: four cores in a square, wire armour, oversheath.
Key specifications
Model: YJV32, copper conductor, XLPE insulated, fine galvanised steel wire armoured, PVC sheathed
Rated voltage: 0.6/1 kV (Um = 1.2 kV)
Cores and cross section: 4 x 50 mm2, three phases plus full size neutral; series covers 4 x 25, 35, 70 and 95 mm2
Conductor: bare copper, class 2 stranded 19/1.78 mm; DC resistance max. 0.387 ohm/km at 20 C
Neutral: full size, same section as the phase cores
Insulation: XLPE, nominal thickness 1.0 mm
Screen: no metallic screen; galvanised fine steel wire armour provides the mechanical protection layer
Sheath: PVC, black; thickness taken from the standard dimension class for the finished diameter and stated on the works order
Standard: GB/T 12706.1-2020; conductor to GB/T 3956
Operating temperature: 90 C continuous; 250 C short circuit for 5 s maximum; ambient at laying min. 0 C
Minimum bending radius: 12 x overall diameter for this multi-core wire armoured construction
Reference current rating: 177 A in air, 187 A direct buried at 25 C, single circuit, three loaded cores. The neutral is a return path and does not add to the rating.
Overall diameter and mass: stated on the works order sheet for the section ordered, because they follow the bedding and sheath build of that production run
Drum length: 500 m standard, cut to order
Four core series
25 mm2: conductor 7/2.14, insulation 0.9 mm, resistance max. 0.727 ohm/km, 118 A in air, 127 A buried
35 mm2: conductor 7/2.52, insulation 0.9 mm, resistance max. 0.524 ohm/km, 145 A in air, 155 A buried
50 mm2: conductor 19/1.78, insulation 1.0 mm, resistance max. 0.387 ohm/km, 177 A in air, 187 A buried
70 mm2: conductor 19/2.14, insulation 1.1 mm, resistance max. 0.268 ohm/km, 224 A in air, 234 A buried
95 mm2: conductor 19/2.53, insulation 1.1 mm, resistance max. 0.193 ohm/km, 273 A in air, 283 A buried
Ratings are at 25 C, single circuit, three loaded cores. Corrections before sizing: ambient 40 C x 0.88, 45 C x 0.83; grouping 2 circuits x 0.85, 3 circuits x 0.75, 4 circuits x 0.68 where spacing is under 2 x diameter.
Six layers, and where the fourth core sits

Layer order from the outside in. The neutral is the fourth core, same section as the others.
- 1 PVC oversheath: moisture and abrasion barrier, thickness from the dimension class of the finished diameter.
- 2 Galvanised steel wire armour: carries the pull in ducts and the self weight of a vertical drop, and takes point load from backfill.
- 3 Extruded bedding: keeps the wires off the insulation, so bending and long term vibration wear the bedding rather than the core surface.
- 4 Fillers: four round cores leave a cross shaped void; filled to a circle so the armour lays evenly and the sheath stays uniform.
- 5 XLPE insulation 1.0 mm: thermoset, so the 90 C conductor rating holds after repeated bending at cleats.
- 6 Copper conductor 19/1.78: 19 strands are softer than a 7 strand build, which matters when the cable is bent around cleats in a shaft.

The layer that carries the pull: galvanised steel wires under the oversheath.
Where it goes

Vertical run cleated in a concrete shaft.
Riser between floors: cleated at each floor, routed clear of the fire main in the shaft, bending radius held at 12 x diameter at the head.
Sub main to a floor board: out of the panel on tray, into a sleeve, then to the floor distribution board that feeds lighting and sockets.
Plant room with mixed load: one run serves the three phase pump set and the single phase maintenance socket beside it; neutral current checked, not assumed.
Duct entry and short buried branch: duct bore at min. 1.5 x diameter, pull tension into the wire layer, buried sections rated from the 187 A figure and corrected for ground temperature.
Standards and tests
GB/T 12706.1-2020: structure and dimensions, insulation and sheath thickness, armour and oversheath requirements, electrical performance, core identification. Four core is a standard core configuration.
GB/T 3956: conductor class 2 strand construction and the 20 C DC resistance limit, 0.387 ohm/km at 50 mm2.
GB/T 2951.11 and 2951.12: tensile strength, elongation at break and air oven ageing retention of the insulation and sheath compounds.
GB/T 3048.4: DC resistance of the finished conductor.
GB/T 3048.5: insulation resistance.
GB/T 3048.8: AC power frequency voltage test on the completed cable.
GB/T 18380.12: vertical flame spread on a single cable; run on the flame retardant ZR- variant, not required for the plain type.
GB/T 17650.1 and 17651.2: halogen acid gas and smoke density; only the low smoke zero halogen WDZ-YJY32 variant is assessed to these.
Routine test report is issued per drum number. Type test reports are supplied when the order scope includes them.
Four core, 3+1, or three core
4 core YJV32: four equal conductors, neutral same section as the phase. Use when the single phase load is substantial, or the neutral may carry close to phase current.
3+1 YJV32: three equal phases plus a reduced neutral. Use where the single phase share is small; saves copper against a full size neutral.
3 core YJV32: no neutral. Use only for balanced three phase load with no single phase branch on the circuit.
Vertical shaft or riser: YJV32 wire armour, cleated at intervals; steel tape armour is not specified to hang weight.
Buried under traffic or rubble: YJV32; tape armour only covers radial crush.
Ambient above 40 C or grouped circuits: apply 0.88 and 0.85 before fixing the section; do not read 177 A or 187 A straight.
Smoke limits in the shaft: WDZ-YJY32 low smoke zero halogen, not this PVC sheath.
Saline or termite ground: YJV33 with PE oversheath, or an anti-termite construction.
FAQ
Is the fourth core a full size neutral?
Yes. All four conductors are the same nominal section, so the neutral can carry the full phase current. If the neutral current is known to be well below the phase current, a 3+1 construction with a reduced neutral saves copper; that is a different product.
What is the difference between 4 core and 3+1?
4 core has four equal conductors. 3+1 has three equal phases plus a smaller neutral for a limited single phase share. They are not interchangeable where the neutral has to be rated for the full phase current.
How many amps will 4 x 50 mm2 carry?
177 A in air and 187 A direct buried at 25 C, on a three loaded core basis, single circuit. Apply the ambient correction (x 0.88 at 40 C) and grouping correction (x 0.85 for two circuits, 0.75 for three) before fixing the section. The neutral is a return path and does not add to the rating.
Can this cable hang in a riser on its own weight?
That is what the steel wire armour is for, but the cable still needs cleats at intervals down the shaft, and the cleat spacing is checked against the vertical load for the section you order. Bending radius is 12 x overall diameter at every cleat and at the head.
What are the overall diameter and weight of 4 x 50 mm2?
They are stated on the works order sheet for the section you buy, because they follow the bedding and sheath build of that production run. A single published figure would be wrong for some drums.
Does the cable come with test reports?
Routine tests (conductor resistance, voltage test, insulation resistance) run on each production length under GB/T 3048 and are reported against the drum number. Third party type test reports are supplied when the order scope includes them.
Notes
Structure and temperature values follow GB/T 12706.1-2020 and GB/T 3956. Current ratings are three loaded core figures at 25 C. Overall diameter and mass are issued on the works order. The four images on this page are illustrations prepared for the product, not photographs of a specific drum.