THHN 10 AWG Stranded Copper Building Wire for 30 A Circuits, 600 V, 90 C Dry
THHN 10 AWG stranded copper wire
,10 AWG building wire 600 V
,THHN wire for 30 A circuits
THHN 10 AWG Stranded Copper Building Wire for 30 A Circuits, 600 V, 90 C Dry
The conductor that leaves the panel for a water heater, a dryer, or the disconnect beside a single phase condenser: 19 strand annealed copper, PVC insulation, nylon jacket, 600 V, 90 C dry, 0.160 in overall.
Table 310.16 puts 10 AWG copper at 30 A in the 60 C column and 40 A in the 90 C column, but NEC 240.4(D)(3) caps the device at 30 A. The 90 C figure is there for derating in a hot roof space, not for a bigger breaker.
It is also the size crews pull when a 20 A circuit sits too far from the source and the voltage drop has to come out of the copper instead of the panel.

10 AWG stranded, cut end. The print legend carries the type, size, temperature rating and flame marking; the strand bundle is 19 wires.
Specifications
Type: THHN, thermoplastic high heat-resistant nylon coated, single conductor building wire
Voltage rating: 600 V
Size and stranding: 10 AWG, 19 strand; solid 10 AWG also available
Conductor: annealed copper to ASTM B3 and B8
Insulation: flame retardant heat resistant PVC, nominal 0.020 in (0.51 mm)
Jacket: polyamide (nylon), nominal 0.004 in (0.10 mm)
Overall diameter: 0.160 in (4.07 mm) stranded, 0.149 in (3.78 mm) solid
Net weight: 38 lb per 1000 ft, so a 500 ft coil is about 19 lb
Temperature rating: 90 C dry location; a wet location rating applies only where the legend carries the THWN or THWN-2 designation
Ampacity: 30 A at 60 C, 35 A at 75 C, 40 A at 90 C per NEC Table 310.16; overcurrent device limited to 30 A by NEC 240.4(D)(3)
Standards: construction to UL 83, conductor to ASTM B3 and B8, installation to NEC Article 310, VW-1 flame marking to UL 2556
Put-up: 500 ft coil, 2500 ft reel, or cut to length
The number people misread

Copper, not more than three current carrying conductors in the raceway. The 90 C column is a derating value, and the device cap sits well below it.
For 10 AWG the gap is 40 A against a 30 A device. That gap is not waste, it is margin: it is what lets the same conductor stay legal inside a conduit with four current carrying conductors, or in a roof space at 45 C, where the correction factors eat into the base figure before the breaker is even chosen.
The other direction matters too. A 20 A circuit on 10 AWG is common practice on long runs, because the conductor can carry the current with less drop while the 20 A breaker still protects it. Upsizing the copper is allowed; upsizing the breaker is not.

Where 10 AWG sits in the usual hierarchy of branch circuits.
Three layers, and what each one does on site
- Annealed copper, 19 strand: finer strands than a 7 wire build, so the conductor deforms evenly under a 30 A lug and the torque holds. It also follows a bend radius in a tight disconnect enclosure without springing back out of the terminal.
- PVC insulation, 0.020 in: one wall thickness up from 12 AWG, which is how UL 83 scales the dielectric margin with conductor size. At 240 V equipment circuits this is the layer that keeps the 600 V rating honest.
- Nylon jacket, 0.004 in: low friction, abrasion resistant, and rated Gas and Oil Resistant II. On a condenser disconnect or a commercial kitchen feed, this is the layer that meets the knockout and the oil.
Where it goes
Electric water heater: 240 V, typically 4500 W, from the panel through a basement or crawl space to the unit. Narrow boxes, metal connectors, and a 30 A breaker at the other end.
Electric dryer: 30 A receptacle circuit, in conduit or a finished assembly, terminating at a 30 A receptacle or a whip.
Single phase condenser disconnect: indoor unit to the disconnect beside the outdoor unit, conduit facing down, wet location enclosure. Confirm the W rating on the legend if the enclosure is rated for wet locations.
Commercial kitchen equipment: single phase 30 A fryer, oven or hot water machine, where oil and washdown are part of the environment and the jacket rating matters.
Long 20 A runs: voltage drop over a long pull, conductor upsized to 10 AWG, breaker unchanged at 20 A.

Color is ordered, not assumed: black, white, red, green and blue are standard, other colors per the color code.
Standards and tests
UL 83: thermoplastic insulated wires and cables. Structure and dimensions, insulation and jacket thickness, voltage withstand, insulation resistance, mechanical properties, heat and moisture resistance.
ASTM B3: annealed copper wire, covering the individual strands.
ASTM B8: concentric lay stranded conductors; 10 AWG stranded is a 19 wire construction.
UL 2556: the VW-1 vertical flame test behind the flame marking on the jacket.
NEC Table 310.16: ampacity, 30 A, 35 A and 40 A for 10 AWG copper at 60 C, 75 C and 90 C.
NEC 240.4(D)(3): the 30 A overcurrent limit for 10 AWG.
NEC 310.15: ambient correction and conductor adjustment inside a raceway.
ICEA S-95-658 and NEMA WC70: general requirements for construction, marking and packaging.
RoHS: restricted substances, carried through for European destinations.
Every production length is continuity and voltage tested, and the print legend carries size, temperature rating and the VW-1 marking.

Standard put-up: 500 ft coil, 2500 ft reel, or cut lengths.
Choosing the size
30 A equipment circuit: 10 AWG copper. Do not downgrade to 12 AWG to save copper; 240.4(D) does not allow a 30 A device on 12 AWG.
20 A circuit with long runs: upsize to 10 AWG and keep the 20 A breaker. This is the legitimate use of the 90 C column.
More than three current carrying conductors, or ambient above 30 C: apply 310.15 first, then compare against 30 A. Do not read the table value straight.
75 C terminations: the 35 A figure applies to the conductor, the device is still 30 A.
Wet location or buried: confirm THWN or THWN-2 on the legend, otherwise specify XHHW-2.
Low smoke or halogen free requirement: PVC will not comply; move to an XLPE or LSZH construction.
FAQ
What size wire do I need for a 30 amp water heater?
10 AWG copper. It is listed at 30 A in the 60 C column of Table 310.16, and 240.4(D)(3) allows a 30 A device on 10 AWG. Check the nameplate and the run length before ordering: a long run may need 8 AWG for voltage drop while the breaker stays at 30 A.
Can I put a 40 A breaker on 10 AWG because the table says 40 A at 90 C?
No. The 90 C column is an ampacity value used with correction and adjustment factors. 240.4(D)(3) limits the overcurrent device for 10 AWG to 30 A. The 90 C figure proves a conductor still has enough ampacity after derating; it does not allow a larger device.
Stranded or solid for a 30 A circuit?
Stranded 19 pulls through conduit and terminates more forgivingly at 30 A lugs. Solid is stiffer and suits long straight runs and switch boxes. Both are 10 AWG, both are UL 83 constructions.
What is the outside diameter, and how much does a coil weigh?
0.160 in for stranded and 0.149 in for solid. 38 lb per 1000 ft, so a 500 ft coil is about 19 lb. One person can carry it, but it is noticeably heavier than the 12 AWG coil most crews are used to.
Does THHN work outdoors at the condenser disconnect?
Only if the print legend carries THWN or THWN-2. Plain THHN is a dry location conductor, and a disconnect enclosure is often a wet location, so confirm the W rating before you buy.
Is this wire UL listed?
The construction follows UL 83 and the conductor follows ASTM B3 and B8. UL listing status and the file number are stated on the order documents for the specific put-up; request the label artwork before the order if the inspector requires it.
Notes
Dimensions and weights are nominal, from published 10 AWG stranded THHN data. Ampacities follow NEC Table 310.16 with the 240.4(D)(3) device limit applied. The photographs are product photographs; the two charts are illustrations prepared for this page from the NEC values, not photographs of a specific spool.